2018-10-01 15:57:58PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PERSON THAT SIGNED THE PLANS IS AND ENGINEER.
 FLORIDA STATUTES 471 AND FAC 61G15 - 23.003 REQUIRE
 PLANS FROM AN ENGINEER TO BE SIGNED, SEALED AND DATED
 BY THE ENGINEER. FBC 107.2.1 - INFORMATION ON
 CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) COMPLIED. THE PLANS THAT WERE SUBMITTED SHOW WOOD
 FRAMING AT THE DOOR OPENINGS. TYPE I AND II
 CONSTRUCTION REQUIRES NONCOMBUSTIBLE MATERIALS FOR THIS
 APPICATION. FBC 603.1 ALLOWS FIRE-RETARDANT-TREATED
 WOOD IN NONBEARING PARTITIONS WHERE THE FIRE-RESISTANCE
 RATING IS 2 HOURS OR LESS. SPECIFY ON THE PLANS THAT
 THE WOOD STUDS AT THE DOOR OPENINGS WILL BE
 FIRE-RETARDANT-TREATED WOOD (FRTW).
  
 3) PARTICAL COMPLIANCE. STILL NEED THE SMOKE AND FLAME
 SPREAD TEST REPORTS FOR THE WHISPER MAT SOUND
 UNDERLAYMENT. ASTM E 84-09
 PROVIDE THE FOLLOWING INFORMATION FOR FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 > DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107.
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 3. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 4. STATED VALUE OF WORK.
 5. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 6. PROPOSED UNDERLAYMENT.
 7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
  
 FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
  
 FBC 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
  
  
  
  
  
  