2018-08-07 17:25:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071182
 8/7/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN ENLARGED MECHANICAL THAT SHOWS THE DUCT
 RELOCATIONS, THE TYPE OF DUCTWORK, THE DUCT SIZES, AND
 THE CFM SUPPLY AT EACH RELOCATED DIFFUSER- SECTION
 107.2.1 WPB.
  
 2) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT, INCLUDING
 THE LEVEL OF ALTERATION PER THE FBC EX.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  