| Plan Review Notes For Permit 18071175 |
| Permit Number |
18071175 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-28 08:30:09 | 1) THE GAS PLAN THAT HAS BEEN SUBMITTED SHOWS AN | | | EXISTING GAS SYSTEM. THERE IS NO RECORD OF A PERMIT FOR | | | A GAS SYSTEM AT THIS ADDRESS SO IT IS ASSUMED THIS WORK | | | WAS INSTALLED WITHOUT A PERMIT. THEREFORE, THE GAS | | | PERMIT MUST INCLUDE ALL THE EXISTING GAS APPLIANCES AND | | | PIPING.WPB AMEND. TO FBC SEC. 105.1. | | | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE | | | COOKTOP PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6 | | | (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1. | | | 3) GAS APPLIANCES SHALL BE LISTED AND LABELED IN | | | ACCORDANCE WITH 2017 FBC-FUEL GAS SEC.301.3. SUBMIT TWO | | | COPIES OF THE MANUFACTURER'S SPECIFICATIONS SHOWING | | | THAT THE COOKTOP AND OTHER GAS APPLIANCES ARE LISTED | | | AND LABELED. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS AND | | | INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS. | | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON | | | THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING | | | INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR | | | CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|