2018-07-28 08:30:091) THE GAS PLAN THAT HAS BEEN SUBMITTED SHOWS AN
 EXISTING GAS SYSTEM. THERE IS NO RECORD OF A PERMIT FOR
 A GAS SYSTEM AT THIS ADDRESS SO IT IS ASSUMED THIS WORK
 WAS INSTALLED WITHOUT A PERMIT. THEREFORE, THE GAS
 PERMIT MUST INCLUDE ALL THE EXISTING GAS APPLIANCES AND
 PIPING.WPB AMEND. TO FBC SEC. 105.1.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 COOKTOP PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6
 (CLOTHES DRYERS) OR 2017 FBC-RES. SEC. G 2407.1.
 3) GAS APPLIANCES SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH 2017 FBC-FUEL GAS SEC.301.3. SUBMIT TWO
 COPIES OF THE MANUFACTURER'S SPECIFICATIONS SHOWING
 THAT THE COOKTOP AND OTHER GAS APPLIANCES ARE LISTED
 AND LABELED.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
  
  