| 2018-07-26 18:08:18 | RESIDENTIAL (R3) ROOFING, BUILDING REVIEW COMMENTS |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED IS MISMATCHED. |
| | FLORIDA PRODUCT APPROVAL COVER CORRESPONDS TO |
| | FL5680-R20 WHILE SPECIFIC ASSEMBLY SUBMITTED IS FOR |
| | FL16732-R10. NEED TO CORRELATE. PROVIDE PRODUCT |
| | APPROVAL COVER PAGE AND APPROVED ASSEMBLIES THAT MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- SELECTED ASSEMBLY FROM FLORIDA PRODUCT APPROVAL |
| | FL16732-R10 DOESN'T MEET THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS IF THE PRODUCT APPROVAL ALLOWS IT. NOTE: |
| | SEE APPROVED ARCHITECTURAL PLANS DRAWING A1 FOR DESIGN |
| | PRESSURES CALCULATED BY THE ARCHITECT OF RECORD. USE |
| | THIS DESIGN PRESSURES FOR RAS 117 CALCULATIONS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 3- - FLAT ROOF PRODUCT APPROVAL WAS REVISED. OWES $150 |
| | FOR REVISION FEES. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |