Plan Review Notes
Plan Review Notes For Permit 18071144
Permit Number 18071144
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-07 12:33:38REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-04 09:41:371ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.3(12)
  
 2. HOT WATER SHALL BE SUPPLIED TO PLUMBING FIXTURES AND
 PLUMBING APPLIANCES PER FBC RES 2801.1.
 THERE IS A WATER HEATER BEING REMOVED ON PLAN SHEET
 D100 WHICH APPARENTLY SERVICED ENTIRE HOUSE WITH THE
 EXCEPTION OF THE MASTER BATH AND THERE IS NO
 REPLACEMENT INDICATED ON PLAN SHEET A103. PROVIDE ON
 PLANS INDICATING TYPE AND CAPACITY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711