| 2018-08-13 09:44:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ONLY ONE SERVICE IS PERMITTED. REVISED PLAN SHOWS |
| | TWO SEPARATE DROPS AND SERVICES TO THE SAME OCCUPANCY. |
| | PROVIDE CORRECTION. NEC 230.2 |
| | 2. FOR THE GENERATOR FEED, A DISCONNECT AND EMERGENCY |
| | STOP BUTTON IS ALSO REQUIRED AT THE BUILDING SERVED. |
| | PROVIDE CORRECTION. NEC 225.32 |
| | 3. PROVIDE BLOCK NOTE THAT THE GENERATOR REQUIRES |
| | SEPARATE PERMIT AND PLAN SUBMITTAL. WPB FBC 105.1 |
| | 4. VALUE FOR WORK STATED ON REVISION APPLICATION |
| | APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE |
| | AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. |
| | FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |