| 2018-07-27 11:31:34 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18071136 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC R 301]COMPLETE THE "SCHEDULE FOR INSTALLATION |
| | OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL |
| | INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL |
| | SPREADSHEET): |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS?PAGE=2 |
| | |
| | WHAT I'M LOOKING FOR IS THE SIZE OF EACH WINDOW AND IF |
| | ITS IN A BEDROOM. JUST LABEL YOUR WINDOWS ON PROPERTY |
| | APPRAISER SHEET AS 1,2..ETC AND LABEL WHICH ONES ARE IN |
| | BEDROOMS. |
| | PUT THE SIZE OF EACH WINDOW ON THE FORM FROM WEBSITE, |
| | OR ON YOUR OWN SPREADSHEET. |
| | YOU DONT NEED TO FILL OUT ALL THE INFO ON THE SHEET. |
| | JUST MARK TYPE OF CONSTRUCTION AS WOOD, PUT THE ROOF |
| | HEIGHT, WHERE IT SAYS DESIGN PRESSURE DERIVED FROM PUT |
| | [FBC R301.2(2), OPENING NUMBER AND OPENING SIZE. FOR |
| | WALL PRESSURE PUT +31.2 & -33.0. IF WINDOW IS LESS THAT |
| | 4 FEET FROM CORNER THAN PUT +31.2 & -41.0(THE PROPOSED |
| | WINDOWS WILL MEET PRESSURES) |
| | ALL OTHER COULMNS ON FORM WON'T APPLY SINCE YOUR USING |
| | IMPACT WINDOWS AND NO SHUTTER IS REQUIRED. |
| | |
| | 2. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN |
| | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW |
| | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE |
| | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE |
| | [FBC ENERGY 402.1.2] |
| | YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF |
| | 0.25 |
| | ASK WINDOW SUPPLIER AND THEY CAN VERIFY THEY WILL MEET. |
| | THE WINDOWS SHOULD COME WITH STICKERS ON THEM. LEAVE |
| | THE STICKERS ON WINDOWS UNTIL YOU PASS INSPECTION. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |