| 2018-10-22 13:01:38 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18071126 |
| | 10/22/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY CONSERVATION. |
| | |
| | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | DINING AND BAR ROOMS- TABLE 403.3.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 3) PROVIDE AN AIR DEVICE SCHEDULE AND INDICATE THE |
| | SUPPLY CFMS AT EACH DIFFUSER ON THE PLAN. SHOW THE |
| | LOCATION OF THE MAIN RETURN GRILL AND PROVIDE |
| | DIMENSIONS- SECTION 603.1 FBC M. |
| | |
| | 4) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307 FBC |
| | M. SHOW THE TYPE OF PRIMARY PIPING, THE PIPING RUN AND |
| | DISCHARGE LOCATION. |
| | |
| | 5) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE |
| | NEW CONDENSER- SECTION 301.15 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |