| 2018-08-25 19:10:30 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. A1A STATES THAT THE EXISTING PARKING LOT IS TO |
| | REMAIN. SEE FBC A 202.1, 202.4, PATH OF TRAVEL IS TO BE |
| | ACCESSIBLE. A2 DOES NOT SHOW ANY ACCESSIBLE SPACES; A1A |
| | DOES NOT SHOW AN ACCESS AISLE FOR THE "EXISTING |
| | HANDICAP PARKING SPACE". AERIALS APPEAR TO SHOW NO |
| | STRIPING. THERE IS NO RECORD OF A PAVING OR RESTRIPE |
| | PERMIT. |
| | |
| | ALSO PLEASE CONFIRM THAT THE "EXISTING RAMP" COMPLIES |
| | WITH FBC ACCESSIBILITY AS I WAS UNABLE TO FIND A PERMIT |
| | FOR THIS WORK. IF IT COMPLIES, PLEASE NOTE THAT YOU |
| | HAVE CONFIRMED COMPLIANCE ON THE PLAN. IF IT DOES NOT |
| | COMPLY, PLEASE REVISE PLAN. |
| | |
| | SEE ALSO PLUMBING COMMENTS. |
| | |
| | 2. A5, SOME NOTES ARE TOO SMALL TO READ, REVISE, FBC |
| | 107. |
| | |
| | 3. FBC B 1004, REVISE PLAN TO INCLUDE OCCUPANCY |
| | CLASSIFICATION AND OCCUPANT LOAD. |
| | |
| | 4. FBC B 107, IF THIS IS A2 WITH AN OCCUPANT LOAD OVER |
| | 50, PANIC BARS REQUIRED. IF REQUIRED, INDICATE THIS |
| | OPTION ON THE DOOR PRODUCT APPROVAL. |
| | |
| | 5. ON THE DOOR PRODUCT APPROVAL, INDICATE WHICH |
| | THRESHOLD OPTION IS SELECTED TO SHOW COMPLIANCE WITH |
| | FBC A 303. |
| | |
| | 6. FIXED GLASS PRODUCT APPROVALS AND ROOF PRODUCT |
| | APPROVALS WERE NOT SUBMITTED. DO YOU WANT FOR THIS TO |
| | BE DEFFERED? FBC 107. |
| | |
| | 7. THIS PROPERTY HAS TWO EXPIRED PERMITS, PLEASE |
| | ADDRESS, FBC 107. |
| | |
| | 8. FBC 107, PRODUCT APPROVALS TO BE REVIEWED BY |
| | DESIGNER OF RECORD. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |