| 2018-07-28 11:37:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. AMPACITY OF WIRE INSUFFICIENT FOR A 1200AMP |
| | COMMERICAL SERVICE. WIRE SIZE IS TYPICALLY 3- SETS OF |
| | 600MCM WITH 3/0G. 310.15 (B)16 NEC 230.42 NEC |
| | |
| | 2. SERVICE SIZE IS BEING INCREASED. PROVIDE ACCURATE |
| | LOAD CALCULATION INCLUDING ALL LOADS. NEC 220 |
| | |
| | 3. EXISTING SERVICE ONE-LINE DIAGRAM SHOWS UPROTECTED |
| | SERVICE CONDUCTORS AND FEEDER CONDUCTORS IN SAME |
| | RACEWAY/GUTTER. PROVIDE CORRECTIONS 230.7 NEC |
| | |
| | 4. SHOW TRANSFORMER SECONDARY CONDUCTORS AND RACEWAY ON |
| | EXISTING AND NEW PROPOSED ONE-LINE DIAGRAM .FBC 107.2.1 |
| | |
| | 5. SHOW BONDING FOR SERVICE ON NEW PROPOSED ONE-LINE |
| | DIAGRAM FBC 107.2.1 |
| | |
| | 6. DISCONNECTS NOT GROUPED AS PER 230.72A NEC ON NEW |
| | PROPOSED ONE-LINE DIAGRAM. WHERE IS DISCONNECT FOR 1ST |
| | METER AFTER 1200AMP MAIN? PROVIDE CORRECTIONS. |
| | |
| | 7. PROVIDE UL/NRTL LISTINGS FOR NEW TAP BOX AND 1200AMP |
| | MAIN. 110.3B NEC, FBC 107.2.1 |
| | |
| | 8. SHOW LOCATION OF ELECTRICAL SERVICE AND NEW TAP BOX |
| | ON SITE PLAN. FBC 107.2.1 |
| | |
| | 9. VALUE SEEMS LOW, VALUE WILL BE ADDRESSED WHEN RE-SUB |
| | COMES IN AND WE HAVE ALL THE MISSING REQUIRED |
| | INFORMATION. FBC 109.3 FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |