| 2018-07-26 10:52:48 | PERMIT # 18071047 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | 2) FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) |
| | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | 3) ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A |
| | LOCK/UNLOCK INDICATOR. |
| | |
| | 4) PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN |
| | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE |
| | MAINTAINED AT ALL TIMES. (AS MARKED ON SHEET A103) |
| | |
| | 5) SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO |
| | THE FIRE ALARM AND SPRINKLER SYSTEM. |
| | |
| | 6) WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| | BE NEEDED. |
| | |
| | |