| Plan Review Notes For Permit 18071014 |
| Permit Number |
18071014 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-30 14:34:42 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS FOR THE MAIN DRAIN.WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 2) SHT. 2 OF 4 & SHT. 4 OF 4 SHOW THE MAIN DRAIN AS 4 | | | INCH BUT SHT. 3 SHOWS THE MAIN DRAIN AS 6 INCH. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|