| 2018-08-27 07:08:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOW VOLTAGE AND HIGH VOLTAGE STILL TOGETHER IN J-BOX |
| | WITHOUT SEPARATION. CANNOT MIX LOW VOLTAGE AND HIGH |
| | VOLTAGE. 725.136B NEC |
| | |
| | 2. NO PREVIOUS/CLOSED OR CURRENT/OPEN ELECTRICAL PERMIT |
| | FOR 1751 PBL BLVD E243. DISCONNECT SWITCH AND TIME |
| | CLOCK ARE NOT EXISTING. LICENSED ELECTRICIAN REQUIRED |
| | FOR INSTALLATION. HOLD ON PERMIT UNTIL LICENSED |
| | ELECTRICAL CONTRACTOR APPLIES FOR SUB PERMIT. |
| | |
| | 3. DISCONNECT WITHIN SIGHT OF SIGN HAS BEEN REMOVED |
| | FROM PLAN, WAS ON PREVIOUS PLAN?? 600.6A1 NEC |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |