2018-11-09 08:55:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3 (NOT PROVIDED, NOTED
 THAT WILL BE PROVIDED BEFORE INSPECTION.)
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3 (NOT PROVIDED AS NOTED
 ON RESPONSE LETTER.)
 4. CORRECTED.
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 (NOT PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2 (LOAD CALCULATION
 PROVIDED DOES NOT INCLUDE ALL LOADS, DOES NOT INCLUDE
 GARAGE PANEL, LOAD FOR TANKLESS HEATER NOT INCLUDED.
 PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE AS
 REQUESTED.)
 10. CORRECTED.
 11. RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS SHALL
 HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9 (NOT PROVIDED.)
 12. LIGHTING MUST MAINTAIN PROPER CLEARANCES FROM THE
 NEAREST POINT OF STORAGE SPACE IN A CLOTHES CLOSET.
 PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12 (NOT
 CORRECTED.)
 13. CORRECTED.
 14. CORRECTED.
 15. CORRECTED.
 16. CORRECTED.
 17. CORRECTED.
 18. CORRECTED.
 19. CORRECTED.
 20. CORRECTED.
 21. CORRECTED.
 22. CORRECTED.
 23. NEW RISER PROVIDED SHOWS 4/0 ALUMINUM WIRE FROM
 METER TO SERVICE DISCONNECT AND FROM SERVICE DISCONNECT
 TO INTERIOR PANELS. THIS WIRE SIZE IS NOT RATED FOR 200
 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); FBC RE
 E3705.1 (NOT CORRECTED.)
 24. FEED TO INTERIOR PANELS FROM SERVICE DISCONNECT IS
 REQUIRED TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR,
 SIZED PER CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1 (ATTEMPTED CORRECTION IS NOT CODE
 COMPLIANT.)
 25. SPECIFY WIRE AND CONDUIT SIZE FOR OVERHEAD MAST TO
 FPL. WPB FBC 107.2.1; NEC 310.15(B)(7); FBC RE E3603.1
 (WIRE SIZE SPECIFIED IS NOT TO CODE.)
 26. GROUNDING ELECTRODE CONDUCTOR SHOULD NOT BE WIRED
 TO METER CAN AND SERVICE DISCONNECT AND INTERIOR PANEL.
 IT IS CONNECTED AT EITHER THE METER CAN OF THE FIRST
 MEANS OF DISCONNECT. PROVIDE CORRECTION. NEC 250.6 (NOT
 CORRECTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  