Plan Review Notes
Plan Review Notes For Permit 18070946
Permit Number 18070946
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-07 13:00:07REVIEW COMPLETED BY JERALD SMITH 0017-P STATUS OF
 REVIEW DENIED!
2018-09-06 16:15:56PERMIT 18070946
 PLUMBING COMMENTS: APPROVED
 1ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET 7 OF 8
 A. WASHING MACHINE MAY NOT DISCHARGE INTO WET VENT FBC
 RES P3108.1
 B. PROVIDE MANUFACTURERS SPEC FOR WASHING MACHINE TO
 INSURE THAT 1 1/2" FIXTURE DRAIN AND STANDPIPE CAN
 ACCOMMODATE DISCHARGE OR INCREASE SIZE OF SAME TO 2".
 102.1.2 2017 WPB AMEND
 B. SHOWER FIXTURE DRAINS ARE UNDERSIZED. SIZE IN
 ACCORDANCE WITH FBC RES P2708.2
 C. SHOWER FIXTURE DRAINS CANNOT DUE TO THE LAW OF
 GRAVITY DISCHARGE INTO THE WASTE RISER ABOVE THE
 LAVATORIES. CONNECT THE FIXTURE DRAINS TO HORIZONTAL
 WET VENT(S) P3108.1 OR CONNECT TO BUILDING DRAIN AND
 INDIVIDUALLY VENT.P3105.1
 D. CONNECT DISHWASHER TO KITCHEN SINK TAILPIECE OR
 DISPOSAL FBC RES P2717.2
 E. ALL WET VENTED BATHROOM GROUP FIXTURE DRAINS ARE TO
 CONNECT INDEPENDENTLY TO WET VENT(S) P3108.1
  
 2. GENERAL NOTES:
 A. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP FBC RES
 2708.4
 B. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON
 HOT WATER TO BATHTUB IS REQUIRED. FBC RES 2713.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711