| 2018-09-07 13:00:07 | REVIEW COMPLETED BY JERALD SMITH 0017-P STATUS OF |
| | REVIEW DENIED! |
| 2018-09-06 16:15:56 | PERMIT 18070946 |
| | PLUMBING COMMENTS: APPROVED |
| | 1ST REVIEW: FBC 2017 6TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. RE: PLAN SHEET 7 OF 8 |
| | A. WASHING MACHINE MAY NOT DISCHARGE INTO WET VENT FBC |
| | RES P3108.1 |
| | B. PROVIDE MANUFACTURERS SPEC FOR WASHING MACHINE TO |
| | INSURE THAT 1 1/2" FIXTURE DRAIN AND STANDPIPE CAN |
| | ACCOMMODATE DISCHARGE OR INCREASE SIZE OF SAME TO 2". |
| | 102.1.2 2017 WPB AMEND |
| | B. SHOWER FIXTURE DRAINS ARE UNDERSIZED. SIZE IN |
| | ACCORDANCE WITH FBC RES P2708.2 |
| | C. SHOWER FIXTURE DRAINS CANNOT DUE TO THE LAW OF |
| | GRAVITY DISCHARGE INTO THE WASTE RISER ABOVE THE |
| | LAVATORIES. CONNECT THE FIXTURE DRAINS TO HORIZONTAL |
| | WET VENT(S) P3108.1 OR CONNECT TO BUILDING DRAIN AND |
| | INDIVIDUALLY VENT.P3105.1 |
| | D. CONNECT DISHWASHER TO KITCHEN SINK TAILPIECE OR |
| | DISPOSAL FBC RES P2717.2 |
| | E. ALL WET VENTED BATHROOM GROUP FIXTURE DRAINS ARE TO |
| | CONNECT INDEPENDENTLY TO WET VENT(S) P3108.1 |
| | |
| | 2. GENERAL NOTES: |
| | A. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED |
| | PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE |
| | TYPES WITH HIGH TEMPERATURE LIMITING STOP FBC RES |
| | 2708.4 |
| | B. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON |
| | HOT WATER TO BATHTUB IS REQUIRED. FBC RES 2713.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |