Plan Review Notes
Plan Review Notes For Permit 18070946
Permit Number 18070946
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-14 07:58:08****CORRECTIONS****
 W.P.B. PERMIT: 18070946 (HOUSE)
 REVIEWED: SEPTEMBER 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH
 EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC AMENDED 105]SEPARATE PERMIT THROUGH ENGINEERING
 FOR DRIVEWAY ACCESS. CONTACT 561-494-1040, OR ON THE
 WEB: HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-
 WORKS/ENGINEERING-SERVICES
  
 1.[FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 2. [FBC R401.3]SITE DRAINAGE PLAN.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
 DRAINAGE PLAN PROVIDED SHOWS FLOW TO THE BACK OF
 PROPERTY. THIS WOULD ALLOW WATER TO ENTER SOUTH LOT.
 PLEASE ADJUST TO MAINTAIN DRAINAGE WITHIN YOUR SITE AND
 SPECIFY WHERE THE NEAREST STORM DRAINS ARE LOCATED.
  
 3. [FBC 107.2.5]SHEET 1 WIND INFORMATION-REMOVE LEVEL
 OF ALTERATION 2. THIS WOULD BE NEW CONSTRUCTION R-3.
  
 4. [FBC R408.4]PROVIDE ACCESS TO THE UNDER FLOOR SPACE
 18X24 MINIMUM.
  
 5. [FBC R301.4]DEAD LOAD AND[FBC R301.5]LIVE LOAD
 PROVIDE LOADS FOR FLOORING ON SHEET 4 AND LOADS FOR
 ROOFING ON SHEET 5.
 ALSO, ADD SPECIES ANS GRADE TO 2X12 JOISTS TO SHOW
 SPANNING MEETS SECTION R502 FOR WOOD FLOOR FRAMING.
  
 6. [FBC TABLE R301.7]ALLOWABLE DEFLECTION FOR FLOOR
 ADDED TO SHEET 4 AND CEILING DEFLECTION ADDED TO SHEET
 5.
  
 7. [FBC R302.9.1 & R302.9.2]FINISHES SHALL HAVE A FLAME
 SPEAD INDEX OF NOT GREATER THAN 200 AND SMOKE DEVELOPED
 INDEX OF NOT GREATER THAN 450.
  
 8. [FBC R602.10]WALL BRACING.
 WHICH METHOD IS BEING USED TO SATISFY BRACING
 REQUIREMENTS? PROVIDE DATA TO SUPPORT THE METHOD IN
 USE.
 HARDIE SIDING REQUIRES BRACED WOOD OR 5/8? SHEATHING.
 PROVIDE BRACING DETAILS TO MEET PRODUCT APPROVAL AND
 CO-ORDINATE BRACING WITH COMMENT ABOVE.
 NOA 18-0504.02 IS HIGHLIGHTED ON HARDIE SIDING
 SUBMITTAL. IF THIS IS BEING USED THAN SUPPLY THAT NOA.
 [FBC AMENDED 107.2.1.2]FL 17184.09 IS MISSING THE
 DRAWINGS PORTION OF PRODUCT APPROVAL. PLEASE PROVIDE 2
 COPIES OF THIS PORTION TO SHOW PRESSURES AND CONNECTOR
 DATA.
  
 9. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS,
 OR INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
 DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO
 INSTALLATION.
  
 10. [FBC R3-1.2(6)]PROVIDE ROOFING WIND DIAGRAM THAT
 MATCHES THE ROOF CONDITION OF THIS HOUSE FOR ZONES
 1,2,& 3.
 SHEET 5 - UPDATE CONNECTOR H10A TO REFERENCE CURRENT FL
 10456.2
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  