| Plan Review Notes For Permit 18070917 |
| Permit Number |
18070917 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-28 04:46:28 | 1) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | | | | PLEASE NOTE: IN THE FUTURE IT IS NOT NECCESSARY TO | | | SUBMIT THE ENTIRE INSTALLATION MANUAL.THE MANUAL MUST | | | BE ON THE JOBSITE FOR INSPECTION. SPECIFICATION SHEETS | | | SHALL BE SUBMITTED SHOWING THE PRODUCT IS LISTED AND | | | LABELED AND THAT THE GAS POOL HEATER HAS A MINIMUM | | | THERMAL EFFICIENCY OF 82%. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|