| Notes |
| Date |
Text |
| 2018-10-10 05:45:59 | PER THE MANUFACTURER'S SPECIFICATIONS FOR THE MAXITROL | | | 325-5AL REGULATOR, THE MAXIMUM INDIVIDUAL LOAD ON THE | | | REGULATOR IS 300,000 BTU'S YET THE GENERATOR IS LISTED | | | AT 473,000 BTU'S. IT APPEARS AS THOUGH THIS REGULATOR | | | CANNOT BE USED FOR THE GENERATOR. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|