Plan Review Notes
Plan Review Notes For Permit 18070905
Permit Number 18070905
Review Stop G
Sequence Number 2
Notes
Date Text
2018-10-10 05:45:59PER THE MANUFACTURER'S SPECIFICATIONS FOR THE MAXITROL
 325-5AL REGULATOR, THE MAXIMUM INDIVIDUAL LOAD ON THE
 REGULATOR IS 300,000 BTU'S YET THE GENERATOR IS LISTED
 AT 473,000 BTU'S. IT APPEARS AS THOUGH THIS REGULATOR
 CANNOT BE USED FOR THE GENERATOR. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved