Plan Review Notes
Plan Review Notes For Permit 18070905
Permit Number 18070905
Review Stop G
Sequence Number 1
Notes
Date Text
2018-07-28 06:37:051) THE GAS PLAN SHOWS THE SYSTEM BEING INCREASED TO 2
 PSI BUT THE SUBMITTED SIZING TABLES ARE BOTH FOR A LESS
 THAN 2 PSI SYSTEM. CLARIFY.SUBMIT TWO COPIES OF THE
 APPLICABLE SIZING TABLES USED TO SIZE THE GAS SYSTEM OR
 PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH
 SIZING TABLE(S) FROM THE GAS CODE OR OTHER STANDARD
 THAT WERE USED IN THE DESIGN OF THIS GAS SYSTEM. REFER
 TO THE 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 2) ) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW