| 2018-07-31 05:59:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NEC 702.5 STATES TRANSFER EQUIPMENT WILL BE SUITABLE |
| | FOR THE INTENDED USE AND DESIGNED AND INSTALLED SO AS |
| | TO PREVENT THE INADVERTANT INTERCONNECTION OF NORMAL |
| | AND ALTERNATE POWER SOURCES. |
| | |
| | THIS DESIGN DOES NOT PREVENT THAT. THE TRANSFER SWITCH |
| | IS NOT SERVICE RATED AND ALSO CONNECTED TO THE LOAD |
| | SIDE OF THE SERVICE DISCONNECTING MEANS FOR THE |
| | APARTMENTS. IF NORMAL POWER WAS RESTORED WHILE THE |
| | TRANSFER SWITCH WAS ENGAGED PROVIDING GENERATOR POWER |
| | THEN THERE WOULD BE SHORT CIRCUIT. PLEASE PROVIDE |
| | CORRECTIONS. |
| | |
| | END OF COMMENTS. |
| | |