Plan Review Notes
Plan Review Notes For Permit 18070905
Permit Number 18070905
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-31 05:59:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NEC 702.5 STATES TRANSFER EQUIPMENT WILL BE SUITABLE
 FOR THE INTENDED USE AND DESIGNED AND INSTALLED SO AS
 TO PREVENT THE INADVERTANT INTERCONNECTION OF NORMAL
 AND ALTERNATE POWER SOURCES.
  
 THIS DESIGN DOES NOT PREVENT THAT. THE TRANSFER SWITCH
 IS NOT SERVICE RATED AND ALSO CONNECTED TO THE LOAD
 SIDE OF THE SERVICE DISCONNECTING MEANS FOR THE
 APARTMENTS. IF NORMAL POWER WAS RESTORED WHILE THE
 TRANSFER SWITCH WAS ENGAGED PROVIDING GENERATOR POWER
 THEN THERE WOULD BE SHORT CIRCUIT. PLEASE PROVIDE
 CORRECTIONS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB