Plan Review Notes
Plan Review Notes For Permit 18070900
Permit Number 18070900
Review Stop G
Sequence Number 1
Notes
Date Text
2018-07-28 07:06:401) THE SUBMITTED GAS PLAN REFERS TO THE 2007 FBC.AND
 ALSO THE 2017 FBC. REMOVE THE REFERENCE TO THE 2007
 FBC.
 2) THE GAS PLAN REFERS TO TABLE 402.4(20). THIS SIZING
 TABLE IS FOR A LESS THAN 2 PSI SYSTEM YET THE GAS PLAN
 CALLS OUT A 2 PSI SYSTEM. CLARIFY.
 3) SHOW THE LOCATION OF ALL SHUTOFF VALVES AND
 REGULATORS. A LISTED SHUTOFF VALVE IS REQUIRED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2017 FBCR SEC.
 G2420.4.
 4) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF
 THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1.
 5) ) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX
 CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL
 BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR. 2017 FBCR SEC. G2422.1 (8), 2017 FBC-FUEL
 GAS SEC. 411.1.3.2.
 6) A SEDIMENT TRAP IS REQUIRED AT THE GENERATOR.2017
 FBC-FUEL GAS SEC.408.4.
 7) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 8) AN MP REGULATOR IS REQUIRED AT THE GENERATOR.
 9) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW