Plan Review Notes
Plan Review Notes For Permit 18070884
Permit Number 18070884
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-20 19:44:5209/19/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A BACKFLOW PERMIT REQUIRED BY A LICENSED CONTRACTOR
 AND MUST BE CERTIFIED BY UTILITIES PRIOR TO FINAL
 INSPECTION. PLEASE CONTACT CITY OF WPB UTILITIES AT
 561-822-2240 FOR FURTHER DIRECTIONS.
  
 2. THE BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CON
 NECTION-CONTROL-MANUAL FOR MORE INFORMATION.
  
 3. ON DOWNSTAIRS AND UPSTAIRS CLEAN OUTS NOT REQUIRED
 ON THE STACK. THE TOILETS MAY RUN FLAT AND ONLY ON VENT
 REQUIRED TO REDUCE VENTING. IN MASTER, A VENT IS
 REQUIRED BETWEEN THE TUB AND SHOWER, 2017 FBC R3101.2
 TRAP SEAL PROTECTION.
  
 4. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
  
 5. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING
 ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED.
 SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS
 PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4"
 IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER,
 BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR
 APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO
 THE MORTAR DOESN'T COVER THEM PER MANUFACTURES
 SPECIFICATIONS. 2017 FBC R2709.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved