| Date |
Text |
| 2018-09-20 19:44:52 | 09/19/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A BACKFLOW PERMIT REQUIRED BY A LICENSED CONTRACTOR |
| | AND MUST BE CERTIFIED BY UTILITIES PRIOR TO FINAL |
| | INSPECTION. PLEASE CONTACT CITY OF WPB UTILITIES AT |
| | 561-822-2240 FOR FURTHER DIRECTIONS. |
| | |
| | 2. THE BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS |
| | REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY |
| | DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION |
| | MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/ |
| | PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CON |
| | NECTION-CONTROL-MANUAL FOR MORE INFORMATION. |
| | |
| | 3. ON DOWNSTAIRS AND UPSTAIRS CLEAN OUTS NOT REQUIRED |
| | ON THE STACK. THE TOILETS MAY RUN FLAT AND ONLY ON VENT |
| | REQUIRED TO REDUCE VENTING. IN MASTER, A VENT IS |
| | REQUIRED BETWEEN THE TUB AND SHOWER, 2017 FBC R3101.2 |
| | TRAP SEAL PROTECTION. |
| | |
| | 4. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A |
| | WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| | OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| | ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| | AND WHIRLPOOL BATHTUB VALVES. |
| | |
| | 5. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE |
| | LINING. THE ADJOINING WALLS AND FLOOR FRAMING ENCLOSING |
| | ON-SITE BUILT-UP SHOWER RECEPTORS SHALL BE LINED. |
| | SHOWER PAN MUST HAVE A SLOPED MORTAR BED THAT IS |
| | PRE-PITCHED BENEATH PRIOR TO LINER INSTALLATION OF 1/4" |
| | IN PER FOOT TOWARD THE DRAIN, MUST HAVE DAM CORNER, |
| | BACKING AROUND THE PERIMETER AND BEFORE FINAL MORTAR |
| | APPLICATION PLACE SOME PEA GRAVEL OVER WEEP HOLES SO |
| | THE MORTAR DOESN'T COVER THEM PER MANUFACTURES |
| | SPECIFICATIONS. 2017 FBC R2709.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | AVAILABLE FROM 1:00 PM TO 4:00 PM |
| | [email protected] |
| | 561-805-6720 |
| | |