| 2018-09-20 20:27:49 | 09/19/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| | AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC. |
| | G2420.4 |
| | |
| | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4. (RANGE AND |
| | OR HEATER) |
| | |
| | 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. INDICATE THE DELIVERY PRESSURE (PSI ON ISOMETRIC) OF |
| | THE SYSTEM ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 |
| | OR 2017 FBC FUEL GAS RES. SEC. G2413.2. |
| | |
| | 5. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES. |
| | SECS. G2426 THRU G2429.1. |
| | |
| | 6. SUBMIT MANUFACTURER'S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| | 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| | |
| | 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| | GAS RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 8. INDICATION ON THE PLAN THAT THE GRILL IS LOCATED |
| | UNDER A ROOF, IT MAY REQUIRE A HOOD PER MANUAL, PLEASE |
| | SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. 2017 |
| | FBC FG RES. SEC.G2408.1. |
| | |
| | 9. SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR AND THEY SHALL BE ONSITE FOR FINAL GAS |
| | INSPECTION. THE GENERATOR SHALL BE LISTED AND APPROVED. |
| | NFPA 58 SEC. 5.20.1. THE GENERATOR SHALL MEET THE |
| | REQUIREMENTS OF UL 2200. |
| | |
| | 10. THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1'-6") |
| | FROM THE HOUSE, FIVE (5'-0") FROM THE PROPERTY LINE, |
| | EXHAUST SHALL BE TEN (10'-0") FROM ANY OPENING UNLESS |
| | OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION |
| | INSTRUCTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |