| 2018-09-24 12:31:40 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18070884 |
| | REVIEWED: SEPTEMBER 24, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | I DID A PARTIAL REVIEW TO TRY AND GET THE INFORMATION |
| | NEEDED FOR A FULL REVIEW ON THE RE-SUBMITTAL. |
| | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | 1. IN DRAWING FOLDER THE PLANS CS-1 AND A001-A601 ARE |
| | IN DWG. FORMAT. PLEASE UPLOAD NEW PLANS IN PDF. FORMAT |
| | WITH DIGITAL SIGNATURE AND PLACE A DIGITALLY CREATED |
| | IMAGE OF YOUR SEAL AND THE FOLLOWING SENTENCES WHERE AN |
| | ORIGINAL SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING |
| | PHYSICALLY SIGNED, DATED AND SEALED. THE SENTENCES CAN |
| | BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE |
| | AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON |
| | THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK. |
| | "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY |
| | [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP |
| | SHOWN USING A DIGITAL SIGNATURE". (SEE SIGNATURE REVIEW |
| | FOR ADDITIONAL REVIEWERS COMMENTS) |
| | |
| | 2. LAYOUTS & FABRICATION DRAWINGS (320 PAGES) WERE |
| | UPLOADED IN BOTH SUPPORTING DOCUMENTS AND DRAWINGS |
| | FOLDER. THIS IS PROBABLY BECAUSE SOME OF THE |
| | INFORMATION IS TYPICALLY IN DRAWINGS (FRAMING PLANS AND |
| | STRUCTURAL PLANS), AND TRUSS ENGINEERING IS USUALLY A |
| | SUPPORTING DOCUMENT. |
| | CAN THIS BE SPLIT UP SO THAT STRUCTURAL DRAWINGS ARE IN |
| | THE DRAWING FOLDER AND SUPPORTING TRUSS PLANS CAN GO IN |
| | SUPPORTING DOCS? |
| | IDEALLY, I WOULD LIKE TO SEE FLOOR FRAMING PLAN, ROOF |
| | FRAMING PLAN AND STRUCTURAL DETAILS ON INDIVIDUAL |
| | DRAWINGS SHEETS TO THE DRAWINGS FOLDER AND THE TRUSS |
| | SHOP DWG?S CAN BE A MULTI PAGE FILE UPLOADED TO THE |
| | SUPPORTING DOCS FILE. |
| | THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | EXCERT FROM DIGITAL PLAN REVIEW GUIDE: |
| | EACH PLAN PAGE SHALL BE SAVED AS A SEPARATE PDF FILE |
| | AND SHOULD BE IN LANDSCAPE FORMAT. CAD DRAWINGS SHALL |
| | BE SAVED INTO A PDF FILE FORMATTED IN SINGLE LAYER |
| | BLACK AND WHITE (MONOCHROME) SETTING. |
| | |
| | 3. IS THIS A PRE-FABRICATED STRUCTURE? IF SO THE |
| | DOCUMENTS FOR THAT PORTION CAN GO INTO THE SUPPORTING |
| | DOCUMENT FOLDER WHILE ON-SITE CONSTRUCTION DRAWINGS |
| | SHOULD BE IN THE DRAWING FOLDER. |
| | |
| | 4. THE PLANS CALL FOR A SPECIAL INSPECTOR. IS THAT |
| | INSPECTOR NEEDED FOR ON-SITE INSPECTIONS? |
| | IF SO CONTACT ME SO I CAN SEND YOU INFORMATION ON WHAT |
| | IS REQUIRED FOR SPECIAL INSPECTOR, OR INDICATE THAT THE |
| | SPECIAL INSPECTOR IS JUST FOR OFF-SITE PRE-FABRICATION. |
| | |
| | 5. SHEET A202 HAS NO DRAWINGS IN IT. PLEASE ADD |
| | DRAWINGS OR REMOVE FROM SET. ARE THE FOUR IDF |
| | RENDERINGS SUPPOSED TO BE IN SHEET A202? THEY WOULD BE |
| | BETTER OFF IN A DRAWING SHEET AS JUST A JPG MAKES THE |
| | DRAWING SET HARDER TO PRINT OUT AS A COMPLETE FIELD |
| | SET. IF THOSE JPGS ARE BEING LOADED TO ATTACH TO A DWG |
| | THEY WILL NOT BE NEEDED ONCE PDF'S REPLACE THE DWG |
| | SHEETS. PLEASE REMOVE THE FOUR IDF RENDERINGS FROM |
| | DRAWINGS FOLDER OR PUT THEM IN SUPPORTING DOCS FOLDER. |
| | |
| | 6. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP |
| | CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| | AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND |
| | ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION |
| | CONTROL |
| | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| | /FORMS,-PERMITS-APPLICATIONS |
| | |
| | 7. PROVIDE SURVEY TO SHOW NEW STRUCTURE ON THE NEWLY |
| | DIVIDED LOT. |
| | |
| | 8. [FBC R401.3]PROVIDE SITE DRAINAGE PLAN. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | [FBC R403.1.7.3] FOUNDATION ELEVATION. |
| | ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| | SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| | AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| | DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| | PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| | THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| | BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| | DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| | ALL LOCATIONS ON THE SITE. |
| | |
| | 9. EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | 10. [FBC R309.1]FLOOR SURFACE. |
| | GARAGE FLOOR SURFACES SHALL BE OF APPROVED |
| | NONCOMBUSTIBLE MATERIAL. |
| | THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR |
| | OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| | VEHICLE ENTRY DOORWAY. |
| | SHOW SLOPE OF GARAGE AS APPLICABLE. |
| | |
| | 11. [FBC R302.5.1] OTHER OPENINGS BETWEEN THE GARAGE |
| | AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD DOORS |
| | NOT LESS THAN 1 3/8 INCHES (35 MM) IN THICKNESS, SOLID |
| | OR HONEYCOMB-CORE STEEL DOORS NOT LESS THAN 1 3/8 |
| | INCHES (35 MM) THICK, OR 20-MINUTE FIRE-RATED DOORS. I |
| | CAN?T SEE CALL OUT ON THE DWG SHEET, BUT THIS WILL |
| | APPLY TO RE-SUBMITTAL. |
| | |
| | 12. [R302.6]GARAGE CEILING TO HAVE TYPE NOT LESS THAT |
| | 5/8? TYPE X OR EQUIVELANT DRYWALL WHEN HABITABLE SPACE |
| | IS PROVIDED ABOVE. SHOW IN PLANS. |
| | |
| | 13. [FBC R807]IF ATTIC ACCESS IS PROVIDED, SHOW ON |
| | PLANS AND PROVIDE DETAIL TO MEET [FBC ENERGY R402.2.4]. |
| | |
| | 14. [FBC ENERGY TABLE R402.2.6]STEEL-FRAME CEILING, |
| | WALL AND FLOOR INSULATION (R-VALUE) |
| | USE THIS TABLE TO DETERMINE R-VALUES NEEDED FOR STEEL |
| | FRAMED CEILINGS, WALLS AND FLOORS. |
| | |
| | 15. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL |
| | (ELP)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW |
| | ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE |
| | SIGNED BY BUILDER AND AVAILABLE FOR INSPECTOR TO REVIEW |
| | FOR BUILDING FINAL. |
| | |
| | 16. [FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS |
| | FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFFERED (RIDGE VENT, SHINGLE AND UNDERLAYMENT) |
| | |
| | 17. [FBC R803.2.3.1]SHEATHING FASTENING. |
| | SHOW HOW ROOF SHEATHING IS ATTACHED TO FRAMING IN ROOF |
| | ZONES 1,2 &3(CONNECTOR AND SPACING). TABLE R804.3 FOR |
| | COLD-FORMED STEEL ROOF FRAMING |
| | |
| | 18. [FBC 1014]GUARDS AND HANDRAILS. [FBC 1607.8]LOADS |
| | ON HANDRAILS AND GUARDRAILS. |
| | PROVIDE HANDRAIL AND GUARDRAIL ENGINEERING, OR INDICATE |
| | THAT YOU WOULD LIKE IT DEFERRED. |
| | |
| | 19. [FBC R318]INDICATE THE MEANS OF TERMITE PROTECTION |
| | PROPOSED AND REFERENCE SECTION R308 FOR STANDARDS. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |