| 2018-08-10 17:11:12 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM PROVIDED BY ELECTRICAL CONTRACTOR IS |
| | NOT ACCEPTABLE. ELECTRICAL CONTRACTOR IS NOT PERMITTED |
| | TO DESIGN 480 VOLT SYSTEMS PER FLORIDA STATUES. PROVIDE |
| | ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED BY A |
| | LICENSED DESIGN PROFESSIONAL. FS 471.003(2)(H); |
| | 471.025; WPB FBC 107.2.1, 107.3.5 |
| | 2. SHEET C1OF THE MODULAR STRUCTURE PLAN STATES THAT |
| | THE BASIS OF DESING IS THE 2011 NATIONAL ELECTRICAL |
| | CODE. THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION. |
| | FBC PREFACE, ALSO SEE CODES ABOVE. |
| | |
| | END OF COMMENTS. |
| | |