2018-08-10 17:11:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED BY ELECTRICAL CONTRACTOR IS
 NOT ACCEPTABLE. ELECTRICAL CONTRACTOR IS NOT PERMITTED
 TO DESIGN 480 VOLT SYSTEMS PER FLORIDA STATUES. PROVIDE
 ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED BY A
 LICENSED DESIGN PROFESSIONAL. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. SHEET C1OF THE MODULAR STRUCTURE PLAN STATES THAT
 THE BASIS OF DESING IS THE 2011 NATIONAL ELECTRICAL
 CODE. THIS IS NOT THE CURRENT CODE. PROVIDE CORRECTION.
 FBC PREFACE, ALSO SEE CODES ABOVE.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved