| Date |
Text |
| 2018-07-27 07:09:05 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. SHOW CONDUIT SIZE, |
| | PATH OF CONDUITS, WHAT PANEL THE LIFT WILL BE FED FROM, |
| | LOAD CALCULATION FOR THE PANEL, OVER CURRENT |
| | PROTECTION, ETC. FS 471.003(2)(H); 471.025; WPB FBC |
| | 107.2.1, 107.3.5 |
| | |
| | 2. CONFLICTING INFORMATION ABOUT MOTORS ON PLAN. SHOWS |
| | BOTH 2X- 3/4HP MOTORS ON PLAN AND ALSO 2X- 1-1/2HP |
| | MOTORS ON PLAN, PLEASE CLARIFY. |
| | |
| | 3. PROVIDE SUBMITTALS FOR BOAT MOTORS FOR PRODUCT |
| | APPROVAL. MUST BE NRTL/UL LISTED. FBC 107.2.1, 110.3B |
| | NEC |
| | |
| | 4. ADDRESS OF PROJECT MUST BE ON PLAN. FBC 107.2.1 |
| | |
| | INFORMATIONAL NOTE: PLEASE SPEAK WITH BUILDING |
| | INSPECTORS AND ENGINEERING ABOUT PENETRATIONS THROUGH |
| | SEA-WALL AND CONDUIT BEING RAN THROUGH CITY EASEMENTS. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |