2018-07-18 17:05:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A DIAGRAM OF THE ROOF AND SHOW THE SIZE AND
 LOCATION OF THE EXISTING SKYLIGHT. FBC-R301.2.1
  
 2) THE ATTACHMENT METHOD AND ATTACHMENT RESISTANCE
 MOMENT HAVE NOT BEEN SPECIFIED FOR THE CONCRETE ROOF
 TILE. SPECIFY THIS INFORMATION OR MARK THE APPROPRIATE
 ITEMS ON THE ROOF TILE PRODUCT APPROVALS. IF AN
 ADHESIVE OR MORTAR IS PROPOSED SUBMIT TWO SETS OF
 PRODUCT APPROVALS FOR THE PRODUCT THAT WILL BE USED.
 FBC 107.2.1 AND FBC-R301.2.1
  
 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 SKYLIGHT (NOA NO.15-0715.08) HAS BEEN SUPERSEDED BY NOA
 NO. 18-0307.10. SUBMIT TWO COPIES OF THE CURRENT
 PRODUCT APPROVAL.