| 2018-07-18 17:05:06 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE A DIAGRAM OF THE ROOF AND SHOW THE SIZE AND | | | LOCATION OF THE EXISTING SKYLIGHT. FBC-R301.2.1 | | | | | | 2) THE ATTACHMENT METHOD AND ATTACHMENT RESISTANCE | | | MOMENT HAVE NOT BEEN SPECIFIED FOR THE CONCRETE ROOF | | | TILE. SPECIFY THIS INFORMATION OR MARK THE APPROPRIATE | | | ITEMS ON THE ROOF TILE PRODUCT APPROVALS. IF AN | | | ADHESIVE OR MORTAR IS PROPOSED SUBMIT TWO SETS OF | | | PRODUCT APPROVALS FOR THE PRODUCT THAT WILL BE USED. | | | FBC 107.2.1 AND FBC-R301.2.1 | | | | | | 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | SKYLIGHT (NOA NO.15-0715.08) HAS BEEN SUPERSEDED BY NOA | | | NO. 18-0307.10. SUBMIT TWO COPIES OF THE CURRENT | | | PRODUCT APPROVAL. |
|