| Notes |
| Date |
Text |
| 2018-08-29 13:41:36 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | I MISSED THAT THIS WAS A POOL PUMP FIRST TIME AROUND. | | | | | | I WILL NEED THE CUTSHEETS FOR THE CONTROLER AND PUMP | | | SHOWING THAT IT IS LISTED FOR USE WITH A POOL. | | | | | | 690.5 REQUIRES GF PROTECTION | | | 690.11 REQUIRES ARC FAULT PROTECTION | | | | | | COULD NOT FIND PS800 CONTROLER. |
|