| Plan Review Notes For Permit 18070704 |
| Permit Number |
18070704 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-20 18:01:07 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THIS IS A CHANGE OF OCCUPANCY PLEASE SHOW ON THE | | | PLAN THE PREVIOUS OCCUPANCY ALONG WITH THE NEW ONE. PER | | | FBC EX CH. 407 | | | | | | 2. PLEASE SHOW THE OCCUPANT LOAD ON THE PLAN. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 3. WITH THE CHANGE OF OCCUPANCY FROM BUSINESS TO | | | ASSEMBLY YOUR OCCUPANT LOAD WILL INCREASE WHICH WILL | | | YOU TO INSTALL A WATER FOUNTAIN AND SERVICE SINK. | | | PER FBC EX 1010.1 AND FBC PL TABLE 403.1, 410.3 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|