| 2018-08-07 16:58:50 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070704 |
| | 8/7/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PROPOSED CHANGE OF OCCUPANCY TO A PLACE OF |
| | WORSHIP MAY REQUIRE INCREASED MECHANICAL VENTILATION AS |
| | NOTED IN SECTION 1009.1 FBC EX. IN ORDER TO VERIFY THE |
| | EXISTING AC SYSTEMS WILL ACCOMODATE THE CHANGE, PLEASE |
| | PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS |
| | AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED CFMS OF |
| | FRESH OUTDOOR AIR, AND THE AMOUNT OF AIR THAT THE |
| | EXISTING SYSTEMS ARE PROVIDING. IN ACCORDANCE WITH |
| | TABLE 403.3.1.1 THE MINIMUM VENTILATION IS BASED ON AN |
| | OCCUPANT DENSITY OF 120 PERSONS PER 1000 SQ. FT. AT A |
| | RATE OF 5 CFMS PER PERSON + 0.06 CFMS PER SQ. FT. |
| | |
| | 2) DESIGN CRITERIA: PLEASE PROVIDE A LIST OF CURRENT |
| | CODES AND STANDARDS USED IN THE DESIGN OF THE PROPOSED |
| | NEW OCCUPANCY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |