| 2018-07-20 09:29:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS INSUFFICIENT INFORMATION PROVIDE TO DO A |
| | COMPLETE AND DETAILED REVIEW OF THIS CHANGE OF |
| | OCCUPANCY. |
| | |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF REVIEW OR DESIGN OF ANY |
| | FIRE CODE. |
| | |
| | THIS PROJECT SHALL COMPLY WITH THE 6TH EDITION OF THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT AND COMPLIANCE. |
| | |
| | |
| | |
| | 3) WHAT WAS THE PREVIOUS OCCUPANCY AND WHAT IS THE |
| | PROPOSED OCCUPNACY PER THE NOTED FFPC ABOVE. |
| | |
| | IT MAY HAVE BEEN BUSINESS AND NOW ASSEMBLY, BUT PLEASE |
| | ENSURE IT IS ACCURATE. |
| | |
| | |
| | |
| | 4) A LIFE SAFETY PLAN IS REQUIRED FOR THIS PROJECT THAT |
| | INCLUDES THE OCCUPANCY TYPE, OCCUPANCY LOAD, TRAVEL |
| | PATHS, EXITS WIDTHS, EMERGENCY LIGHTS, DOOR SCHEDULE, |
| | EXIT HARDWARE, DOOR LOCK TYPES, SEATING PLAN, ETC. |
| | |
| | PLEASE PROVIDE A DETAILED PLAN SHEET. |
| | |
| | |
| | |
| | 5) A STAGE IS INDICATED WITH NO DETAIL. |
| | |
| | PLEASE PROVIDE DETAILS INCLUDING, BUILDING MATERIAL, |
| | HEIGHT, STEPS, HANDRAILS, SPRINKLER PROTECTION, AND |
| | EXACT LOCATION WITH SPECIFIC DIMENSIONS FROM ALL WALLS. |
| | |
| | |
| | |
| | 6) CHAIRS ARE INDICATED WITH NO DETAIL. |
| | |
| | A SEATING PLAN SHALL BE PROVIDED AS PART OF THE LIFE |
| | SAFETY PLAN, INCLUDING CHAIR TYPE, NUMBER OF CHAIRS, |
| | AND AISLE(S) WIDTH. |
| | |
| | ALL DIMENSION SHALL COMPLY WITH NFPA 101, CHAPTER 7, |
| | MEANS OF EGRESS AND CHAPTER 12, NEW ASSEMBLY |
| | OCCUPNACIES. |
| | |
| | |
| | |
| | 7) A FIRE ALARM IS NOT INDICATED. |
| | |
| | BASED ON THE OCCUPANY AND OCCUPANCY LOAD A FIRE ALARM |
| | IS LIKELY REQUIRED. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT AND COMPLIANCE TO PROVIDE A FIRE ALARM |
| | UNDER SEPARATE SHOP DRAWING BY A LICENSED FIRE ALARM |
| | CONTRACTOR. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |