Plan Review Notes
Plan Review Notes For Permit 18070704
Permit Number 18070704
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-25 15:25:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLANS LACK A SUBSTANTIAL AMOUNT OF INFORMATION, SO A
 COMPLETE PLAN REVIEW CANNOT BE DONE. INFORMATION NOT
 PROVIDED:
  
 OCCUPANT LOAD
 EXIT CAPACITIES
 PANIC BARS ON DOORS
 PREVIOUS OCCUPANCY, PROPOSED OCCUPANCY (FBC B CHAPTER
 3)
 COMPLIANCE WITH ALL REQUIREMENTS OF FBC EXISTING
 BUILDING CHAPTER 10
 LEVEL OF ALTERATION
  
 2. PROVIDE A DETAIL FOR THE STAGE, FBC 107. WILL THIS
 BE ACCESSIBLE (RAMP)?
  
 3. PLANS ARE TO BE ARCHITECTURAL QUALITY, DRAWN TO
 SCALE, FBC 107.
  
  
  