2018-08-10 13:08:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. SINCE
 THIS IS LSITED AS MULTI-FAMILY ON THE PROPERTY
 APPRAISERS WEBSITE, THE ELECTRICAL PAGES WILL NEED TO
 BE DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL
 OR ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION.
 WPB FBC 107.1, 107.2; FS 471, 481
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. LOAD CALCULATION IS DIFFICULT TO READ. IT
 APPEARS THE SERVICE CALCULATION SHOWS THE TOTAL SQUARE
 FOOTAGE, BUT DOES NOT SHOW BOTH RANGES, OR BOTH DRYERS.
 ALL LOADS NEED TO BE INCLUDED. NEC 220; FBC RE E3602.2
 3. RISER DIAGRAM SHOWS 2/0 WIRE FOR FEED, BUT THE LOAD
 CALCULATION IS NOT CORRECT. IT IS POSSIBLY CORRECT, BUT
 PROVIDE CORRECT SIZE OF WIRE IN MAST FOR TOTAL LOAD
 WHEN COMPUTED IF DIFFERENT. NEC 310.15
 4. RISER DIAGRAM SHOWS # 2 WIRE FEEDING SUB-PANELS THAT
 HAVE A 150 AMP MAIN BREAKER. THIS WIRE SIZE IS NOT
 RATED FOR 150 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(7) AND (B)(16); FBC RE E3603.1, E3705.1
 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 6. PROVIDE AIC RATING OF SERVICE PANELS. NEC 110.3,
 110.9; FBC RE E3603.3
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 8. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 9. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER