| Plan Review Notes For Permit 18070681 |
| Permit Number |
18070681 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-23 08:30:09 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18070681 | | | REVIEWED: AUGUST 23, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | [FBC R302.3]TWO-FAMILY DWELLINGS. | | | DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE | | | SEPARATED FROM EACH OTHER BY WALL AND FLOOR ASSEMBLIES | | | HAVING NOT LESS THAN A 1-HOUR FIRE-RESISTANCE RATING | | | WHERE TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263. | | | FIRE-RESISTANCE-RATED FLOOR/CEILING AND WALL ASSEMBLIES | | | SHALL EXTEND TO AND BE TIGHT AGAINST THE EXTERIOR WALL, | | | AND WALL ASSEMBLIES SHALL EXTEND FROM THE FOUNDATION TO | | | THE UNDERSIDE OF THE ROOF SHEATHING. | | | | | | [FBC 107.2.5]PROVIDE ANY DETAILS APPLICABLE TO NEW WORK | | | MEETING FIRE RESISTANCE REQUIREMENTS. | | | | | | [FBC 107.2.5]WHAT IS THE CURRENT STRUCTURAL CEILING | | | MATERIAL, AND WHAT WILL BE INSTALLED. PROVIDE DETAIL TO | | | SHOW ATTACHMENT OF SOFFIT TO EXISTING CEILING. | | | | | | |
|