2018-07-27 13:12:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070661
 7/27/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLAN DOES NOT CLEARLY SHOW HOW AIR TO THE LIVING
 ROOM AND BEDROOM #1 WILL BE RETURNED TO THE NEW HEAT
 PUMP. IS THERE A LOUVERED DOOR OR RETURN GRILL AT THE
 HEAT PUMP CLOSET? SEE SECTION 601.6 FBC M.
  
 2) THE RETURN DUCT FROM THE BEDROOM #2 SUITE IS
 UNDERSIZED PER SECTION 601.6(3). THE DUCT SHALL BE
 SIZED LARGE ENOUGH TO RETUN ALL AIR FROM THE SUITE
 INCLUDING THE BEDROOM AND THE CLOSETS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  