| 2018-07-31 11:44:51 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18070655 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC 109]PROVIDE COPY OF PROPOSAL WITH CONTRACTOR TO |
| | SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN ON PERMIT |
| | APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL COST OF |
| | WORK. VALUE WILL BE FOR ALL WORK INCLUDING MECHANICAL |
| | AND ELECTRICAL. |
| | |
| | 2. [FBC 107.2.5]HEAD AND SILL DETAIL ARE FOR WOOD FRAME |
| | 2X6. PROVIDE DETAILS FOR SITE CONDITIONS(2X4 |
| | CONSTRUCTION AND MASONRY CONSTRUCTION). |
| | ALSO, BUCK DETAILS FOR BOTH CONDITIONS. |
| | |
| | 3. [FBC 107.2.5]PROVIDE INFILL DETAILS IF OPENINGS ARE |
| | BEING ADJUSTED. |
| | |
| | 4. [FBC 107.2.5]THE WINDOW PRODUCT APPROVAL ALLOWS FOR |
| | OPENINGS UP TO 52". |
| | PLEASE ADJUST WINDOWS TO MEET PRODUCT APPROVAL. I WOULD |
| | SUGGEST A WINDOW SCHEDULE. SELECT WINDOW TYPE FOR WALL |
| | TYPE (NAIL FIN OR THROUGH FRAME, IF WINDOW IS EGRESS, |
| | PROVIDE BOTH R.O. AND WINDOW SIZE FOR EACH |
| | WINDOW.(WINDOW SCHEDULE) |
| | |
| | 5. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN |
| | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW |
| | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE |
| | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE |
| | R402.1.2. |
| | YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF |
| | 0.25THE WINDOWS SHOULD COME WITH STICKERS ON THEM. |
| | LEAVE THE STICKERS ON WINDOWS UNTIL YOU PASS |
| | INSPECTION. |
| | |
| | 6. [FBC R317.1] 5.WOOD SIDING, SHEATHING AND WALL |
| | FRAMING ON THE EXTERIOR OF A BUILDING HAVING A |
| | CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE |
| | GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED |
| | VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO |
| | SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE |
| | WEATHER. |
| | |
| | 7. WHEN RE-SUBMITTING HAVE THE PERMIT APPLICATION |
| | NOTARIZED. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |