| Plan Review Notes For Permit 18070650 |
| Permit Number |
18070650 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-17 15:02:02 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THIS PERMIT APPEARS TO INDICATE A TCO FOR THE UNIT | | | 5A TO BE USED AS A BUSINESS OFFICE. | | | | | | PLEASE CONFIRM AND PROVIDE SPECIFIC DETAILS ON HOW THIS | | | SPACE WILL BE USED AND WHO WILL USE IT, INCLUDING THE | | | GENERAL PUBLIC AND/OR OUTSIDE CONSTRUCTION RELEATED | | | PERSONS, I.E ARCHITECTS, DESIGNERS, REALESTATE, ETC. | | | | | | | | | | | | | | | 2) THE SUBMITTED PLANS DO NOT INDICATE ANY FIRE ALARM | | | DEVICES WITHIN THE UNIT. | | | | | | PLEASE PROVIDE A NOTE INDICATING THAT THE FA WILL BE | | | FULLY FUNCTIONAL. | | | | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF THE STATUS OF THE | | | STAIRWELLS AS COMPLETE AND CODE COMPLIANT EXITS | | | INCLUDING HANDRAILS, EMERGENCY LIGHTING. EXIT HARDWARE, | | | ETC. | | | | | | PLEASE PROVIDE DETAILS | | | | | | | | | | | | | | | 4) THERE ARE NO INDICATIONS ON HOW THE ENTRANCE INTO | | | THE CONSTRUCTION FLOORS FROM THE STAIRWELL WILL BE | | | CONTROLLED. PERSONS NOT RELATED TO THE BUILDING OR | | | CONSTRUCTION CAN NOT HAVE ACCESS TO THE CONSTRUCTION | | | AREA, | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|