2018-07-17 15:02:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THIS PERMIT APPEARS TO INDICATE A TCO FOR THE UNIT
 5A TO BE USED AS A BUSINESS OFFICE.
  
 PLEASE CONFIRM AND PROVIDE SPECIFIC DETAILS ON HOW THIS
 SPACE WILL BE USED AND WHO WILL USE IT, INCLUDING THE
 GENERAL PUBLIC AND/OR OUTSIDE CONSTRUCTION RELEATED
 PERSONS, I.E ARCHITECTS, DESIGNERS, REALESTATE, ETC.
  
  
  
  
 2) THE SUBMITTED PLANS DO NOT INDICATE ANY FIRE ALARM
 DEVICES WITHIN THE UNIT.
  
 PLEASE PROVIDE A NOTE INDICATING THAT THE FA WILL BE
 FULLY FUNCTIONAL.
  
  
  
  
 3) THERE ARE NO INDICATIONS OF THE STATUS OF THE
 STAIRWELLS AS COMPLETE AND CODE COMPLIANT EXITS
 INCLUDING HANDRAILS, EMERGENCY LIGHTING. EXIT HARDWARE,
 ETC.
  
 PLEASE PROVIDE DETAILS
  
  
  
  
 4) THERE ARE NO INDICATIONS ON HOW THE ENTRANCE INTO
 THE CONSTRUCTION FLOORS FROM THE STAIRWELL WILL BE
 CONTROLLED. PERSONS NOT RELATED TO THE BUILDING OR
 CONSTRUCTION CAN NOT HAVE ACCESS TO THE CONSTRUCTION
 AREA,
  
 PLEASE PROVIDE DETAILS.
  
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  