Plan Review Notes
Plan Review Notes For Permit 18070641
Permit Number 18070641
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-23 12:03:271ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P3.3.1 THE 6" OVERFLOW DRAIN DISCHARGING ON THE
 WEST SIDE OF THE BUILDING WITH 5718 SQFT ON IT IS
 UNDERSIZED IT SHALL BE 8". PER FBC PL TABLE 1106.3
  
 2. SHT. P3.3.1 THERE ARE SEVERAL SECTION OF THE STORM
 DRAIN THAT ARE MISSING THE SQFT I CAN NOT CHECK THE
 SIZING CALCULATIONS WITH OUT THESE NUMBERS PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. P3.2.1 A TWO WAY CLEAN OUT IS REQUIRED BETWEEN EACH
 GREASE INTERCEPTOR PLEASE SHOW ON ISOMETRIC . PER
 MANUFACTURE SPECIFICATIONS AND WPB UTIL. DEPT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  