| 2018-08-23 12:03:27 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. P3.3.1 THE 6" OVERFLOW DRAIN DISCHARGING ON THE |
| | WEST SIDE OF THE BUILDING WITH 5718 SQFT ON IT IS |
| | UNDERSIZED IT SHALL BE 8". PER FBC PL TABLE 1106.3 |
| | |
| | 2. SHT. P3.3.1 THERE ARE SEVERAL SECTION OF THE STORM |
| | DRAIN THAT ARE MISSING THE SQFT I CAN NOT CHECK THE |
| | SIZING CALCULATIONS WITH OUT THESE NUMBERS PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. P3.2.1 A TWO WAY CLEAN OUT IS REQUIRED BETWEEN EACH |
| | GREASE INTERCEPTOR PLEASE SHOW ON ISOMETRIC . PER |
| | MANUFACTURE SPECIFICATIONS AND WPB UTIL. DEPT. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |