Plan Review Notes
Plan Review Notes For Permit 18070641
Permit Number 18070641
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-14 15:16:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E1.1.1 SHOWS AN EXHAUST FAN INSTALLED ABOVE
 THE 1200 AMP DISCONNECT. PROVIDE CORRECTION. NEC
 110.26(E)(1)
 2. FYI ONLY, THIS IS NOT A CODE VIOLATION. I NOTICED
 THE FEEDERS FOR THE 1200 AMP SERVICE ARE INSTALLED IN
 FOUR 3.5 INCH CONDUITS. HOWEVER, THERE ARE ONLY THREE 4
 INCH CONDUITS THAT LEAVE THE 1200 AMP DISCONNECT TO THE
 RESTAURANT. THIS WOULD POSSIBLY REQUIRE COPER WIRE TO
 MEET AMPACITY REQUIREMENT. POSSIBLE OVERSIGHT. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  