| 2018-08-16 18:01:41 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHEET LS.1.0 SPECIFIES THIS BUILDING AS CONSTRUCTION | | | TYPE III-B WITH 2 HOUR FIRE RATED EXTERIOR BEARING | | | WALLS. PROVIDE DETAILS OF EACH OF THE 2 HOUR FIRE RATED | | | EXTERIOR WALL TYPES AND THEIR LISTED ASSEMBLIES. FBC | | | 107.2.1 & FBC 704 | | | | | | 2) THE EXTERIOR STEEL COLUMNS LOCATED IN THE EXTERIOR | | | WALLS ARE REQUIRED TO BE 2 HOUR FIRE PROTECTED. PROVIDE | | | A DETAIL SHOWING HOW THIS PROTECTION WILL BE PROVIDED. | | | FBC 704.2 | | | | | | 3) SHEET LS.1.0 SPECIFIES THIS BUILDING AS A TWO STORY | | | STRUCTURE. IT APPEARS THAT THE VESTIBLE AND BATHROOMS | | | SHOWN ON THE ROOF/TERRACE LEVEL SHOULD BE CONSIDERED A | | | THIRD FLOOR. PLEASE REVISE THE PLANS ACCORDINGLY. FBC | | | 202 | | | | | | | | 2018-08-14 13:16:25 | NOTE FOR BUILDING REVIEW: ELECTRICAL ROOM HAS CHANGED | | | LAYOUT AND IS NOW SHOWN AS EXITING INTO STAIRWELL. THIS | | | IS NOT REFLECTED ON LIFE SAFETY PLAN AS A REVISION, BUT | | | IS SHOWN ON ELECTRICAL SHEET AS A CHANGE. FYI |
|