Plan Review Notes
Plan Review Notes For Permit 18070641
Permit Number 18070641
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-16 18:01:41PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET LS.1.0 SPECIFIES THIS BUILDING AS CONSTRUCTION
 TYPE III-B WITH 2 HOUR FIRE RATED EXTERIOR BEARING
 WALLS. PROVIDE DETAILS OF EACH OF THE 2 HOUR FIRE RATED
 EXTERIOR WALL TYPES AND THEIR LISTED ASSEMBLIES. FBC
 107.2.1 & FBC 704
  
 2) THE EXTERIOR STEEL COLUMNS LOCATED IN THE EXTERIOR
 WALLS ARE REQUIRED TO BE 2 HOUR FIRE PROTECTED. PROVIDE
 A DETAIL SHOWING HOW THIS PROTECTION WILL BE PROVIDED.
 FBC 704.2
  
 3) SHEET LS.1.0 SPECIFIES THIS BUILDING AS A TWO STORY
 STRUCTURE. IT APPEARS THAT THE VESTIBLE AND BATHROOMS
 SHOWN ON THE ROOF/TERRACE LEVEL SHOULD BE CONSIDERED A
 THIRD FLOOR. PLEASE REVISE THE PLANS ACCORDINGLY. FBC
 202
  
  
2018-08-14 13:16:25NOTE FOR BUILDING REVIEW: ELECTRICAL ROOM HAS CHANGED
 LAYOUT AND IS NOW SHOWN AS EXITING INTO STAIRWELL. THIS
 IS NOT REFLECTED ON LIFE SAFETY PLAN AS A REVISION, BUT
 IS SHOWN ON ELECTRICAL SHEET AS A CHANGE. FYI