| Plan Review Notes For Permit 18070635 |
| Permit Number |
18070635 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-19 09:58:30 | | | | | | | | | | | | | ***VALUATION ADDD REPAIRS | | | - | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE INFILL DETAILS A, B, C AND E: | | | A) COORDINATE WOOD STUDS AND CONNECTORS. 2X10 WOOD | | | STUDS CAN NOT BE INSTALLED WITH SIMPSON SP6 CONNECTORS. | | | B) PROVIDE CLEAR SPECIFICATIONS FOR ATTACHMENT OF TOP | | | AND BOTTOM PLATES. TAPCON SIZE IS NOT CLEAR. ARCHITECT | | | OF RECORD TO VERIFY THAT ANCHOR SPACING IS ADEQUATE TO | | | RESIST THE WIND LOADS. |
|