| Plan Review Notes For Permit 18070523 |
| Permit Number |
18070523 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-12-10 14:02:08 | BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE | | | INFORMATION PRIOR TO INSTALLATION AND INSPECTION TO | | | AVOID CONFLICTS/DELAYS): | | | 1- FLOORING SOUND INSULATION: | | | A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE | | | DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS | | | (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90. | | | C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS | | | (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492. | | | NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. | | | | | | 2- THIS IS A THRESHOLD BUILDING AND THE SCOPE OF WORK | | | INCLUDES ALTERATION OF THE STRUCTURAL DESIGN OF THE | | | BUILDING. SPECIAL INSPECTOR WILL BE REQUIRED FOR | | | INSPECTIONS AT THE SHEARWALL. SEC. 110.8 CITY | | | AMENDMENTS. | | | NOTE: PLEASE CONTACT KEN CONRAD (561-805-6666) OR | | | RICHARD GATHRIGHT (561-805-6679) PRIOR TO START OF | | | WORK. | | | | | | 3- THRESHOLD BUILDING: ONLY GENERAL CONTRACTOR CAN DO | | | STRUCTURAL WORK. SEC. 110.3.7.5 CITY AMENDMENTS. |
|