| Plan Review Notes For Permit 18070499 |
| Permit Number |
18070499 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-31 15:44:40 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | RISER DIAGRAM DOES NOT SHOW SIZE OF MAIN AT | | | GENERATOR??? 215.5 | | | | | | WIRE SIZES SHOWN ARE ONLY GOOD UP TO 800A???? 240.4(B) | | | | | | WHAT SIZE IS THE TRANSFER SWITCH? 215.5 |
|