Plan Review Notes
Plan Review Notes For Permit 18070499
Permit Number 18070499
Review Stop E
Sequence Number 2
Notes
Date Text
2018-08-31 15:44:40FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM DOES NOT SHOW SIZE OF MAIN AT
 GENERATOR??? 215.5
  
 WIRE SIZES SHOWN ARE ONLY GOOD UP TO 800A???? 240.4(B)
  
 WHAT SIZE IS THE TRANSFER SWITCH? 215.5