| 2018-07-17 08:39:28 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE TEST REPORTS FOR UNDERLAYMENT AS FOLLOWS: | | | 1A. ASTM E-84 FLAME SPREAD. | | | 1B. ASTM E-90 AIRBORNE SOUND. | | | 1C. ASTM E-492 IMPACT SOUND. | | | | | | FBC 603.1 FLAME SPREAD ? ASTM E-84-09 | | | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE | | | AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT | | | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 | | | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 492. | | | | | | |
|