| 2018-07-13 08:46:37 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | NEED TO LAYOUT THE SCOPE OF THIS PROJECT. WHAT IS THE |
| | ACTUAL WORK INVOLVED. |
| | |
| | PLANS NEED TO SIGNED AND SEALED BY AND ENGINEER |
| | |
| | CONDUCTOR SIZES NOT SHOWN ON PLANS, PLEASE INDICATE |
| | SIZE AND TYPE OF CONDUCTORS TO BE USED (CUT SHEETS) |
| | |
| | PLANS SHOWS CONDUITS COMING FROM A MV MANHOLE TO |
| | BUILDING AND THEN INTO THE SWITCHGEAR WITH NO |
| | DISCONNECT OR OVER CURRENT PROTECTION.. |
| | |
| | 230.205 DISCONNECTING MEANS |
| | (A) LOCATION. THE SERVICE DISCONNECTING MEANS SHALL BE |
| | LOCATED IN ACCORDANCE WITH 230.70. |
| | |
| | 230.70 GENERAL |
| | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE |
| | C ONDUCTORS. |
| | |
| | (1) READILY ACCESSIBLE LOCATION. THE SERVICE |
| | DISCONNECTING MEANS SHALL BE INSTALLED AT A READILY |
| | ACCESSIBLE LOCATION EITHER |
| | OUTSIDE OF A BUILDING OR STRUCTURE OR INSIDE NEAR EST |
| | THE POINT OF ENTRANCE OF THE SERVICE CONDUCTORS. |
| | |
| | 300.50 UNDERGROUND INSTALLATIONS |
| | (A) GENERAL. UNDERGROUND CONDUCTORS SHALL BE IDENTIFIED |
| | FOR THE VOLTAGE AND CONDITIONS UNDER WHICH THEY ARE |
| | INSTALLED. DI RECTBURIAL |
| | CABLES SHALL COMPLY WITH THE PROVISIONS OF 310.10(F). |
| | UNDERGROUND CABLES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH |
| | 300.50(A)(1), (A)(2), OR (A)(3), AND THE INSTALLATION |
| | SHALL MEET THE DEPTH REQUIREMENTS OF TABLE 300.50 |
| | |
| | BASED ON PLAN THE VALUE OF THE WORK SHOWN SEEMS LOW |
| | PLEASE SUBMIT A SIGNED CONTRACT FROM CITY OF WPB. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA |
| | OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL |