| 2018-12-27 09:21:42 | MECHANICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 3RD REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE MECHANICAL PLAN FOR PROPOSED WORK. SUBMITTAL |
| | INCLUDES TWO PAGES MARKED EXISTING MECHANICAL. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2. PROVIDE ENERGY SUBMITTAL. |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | _ OR _ |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| | (MANDATORY). |
| | THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY |
| | PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND |
| | CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT |
| | BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY. |
| | FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)] |
| | REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN |
| | ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND |
| | NON-PRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD |
| | CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE |
| | LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A |
| | DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT |
| | THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE |
| | BUILDER ACCURATELY REFLECTS THE PLANS AND |
| | SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE |
| | FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE |
| | FOUND IN APPENDIX C. |
| | |
| | 3. PROPERTY IS LOCATED IN FLOOD ZONE AE WITH A BASE |
| | FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD. IF A NEW |
| | CONDENSING UNIT IS INSTALLED IT MUST SET AT OR ABOVE |
| | THE DESIGN FLOOD ELEVATION (DFE) OF 9.0 FEET NAVD. |
| | |
| | 4. PROVIDE EXHAST FOR PROPOSED BATHROOM PER TABLE |
| | M1507.4. |
| | |
| | 5. PROVIDE BALANCED AIR RETURNS FOR NEW MECHANICAL |
| | SYSTEM PER SECTION M1602. |
| | |
| | 6. NEW DUCT WORK SHALL BE DESIGNED TO COMPLY WITH |
| | SECTION M1601. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |