Text |
| 2018-09-30 15:25:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. TANKLESS WATER HEATER AND LOCATION OF NEW INTERIOR |
| | PANEL NOT ON PLAN, PROVIDE LOCATION. FBC 107.2.1 (NOT |
| | ADDRESSED) |
| | |
| | 2. MINIMUM OF 2 GROUND RODS REQUIRED 250.53A2 NEC (NOT |
| | ADDRESSED) |
| | |
| | 3. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL |
| | SERVICE. OVERHEAD SERVICE? UNDERGROUND SERVICE? WIRE |
| | SIZE? NEC 220.16A1&2, 220.12, 220.14 |
| | FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1 (NOT |
| | ADDRESSED) |
| | |
| | 4. A/C COMPRESSORS AND AHU'S FED FROM METE/MAIN COMBO |
| | NOT IN LOAD CALC, ALSO TANKLESS WATER HEATER NOT IN |
| | LOAD CALC. PROVIDE ACCURATE LOAD CALCULATION INCLUDING |
| | ALL LOADS. NEC 220; FBC RE E3602.2 (NOT ADDRESSED) |
| | |
| | 5. HOUSE HAS ATTACHED GARAGE. SMOKE ALARMS OF OUTSIDE |
| | OF BEDROOMS MUST BE SMOKE/CARBON MONOXIDE COMBINATION |
| | ALARMS WITHIN 10'. FBC R 315.1 FBC R 315.13 (NOT |
| | ADDRESSED) |
| | |
| | 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS FOR ALL PANELS (METER/MAIN COMBO HAS NO PANEL |
| | SCHEDULE), THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; |
| | WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT ADDRESSED) |
| | |
| | INFORMATIONAL NOTE: TO MY KNOWLEDGE A 300AMP METER/MAIN |
| | COMBO IS NOT SOLD PLEASE VERIFY AND PROVIDE MORE |
| | INFORMATION. FBC 107.2.1 (NOT ADDRESSED) |
| | |
| | NEW COMMENT: |
| | |
| | 7. PLAN SHOULD BE SUBMITTED AS 2 COMPLETE SETS. |
| | CURRENTLY, IT APPEARS THERE IS ONLY ONE SET IN PACKAGE |
| | AND A LOT OF ADDITIONAL SHEETS, MANY WHICH APPEAR TO BE |
| | OLD SHEETS FROM FIRST REVIEW. THIS REVIEWER IS NOT ABLE |
| | TO DETERMINE WHAT IS THE NEW SUBMISSION. A RESPONSE |
| | LETTER ADDRESSING THE ELECTRICAL COMMENTS COULD NOT BE |
| | FOUND. FURTHER COMMENT MAY BE NECESSARY AS MUSH OF THE |
| | INFORMATION REQUESTED IS MISSING FROM THIS SUBMISSION. |
| | WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |