2018-12-26 13:42:06****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 3RD REVIEW:
  
 PLEASE ADDRESS COMMENTS BELOW:
  
 1) COMPLIED LAST REVIEW.
  
 2) COMPLIED LAST REVIEW.
  
 3) COMPLIED LAST REVIEW.
  
 4) NOT COMPLIED. WE STILL NEED THE REGISTERED DESIGN
 PROFESSIONAL'S SIGNATURE, SEAL, AND TITLE BLOCK ON EACH
 PAGE/DOCUMENT AS PER LAST REVIEW:
 THE STRUCTURAL PLANS ARE REQUIRED TO HAVE THE
 ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE IN THE TITLE
 BLOCK ON EACH SHEET. FAC 61G15?23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15?23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 5) COMPLIED (NOT APPLICABLE).
  
 6) NOT COMPLIED. THE SUBMITTED DOCUMENTATION (FLORIDA
 BUILDING CODE, ENERGY CONSERVATION AND ENERGY
 PERFORMANCE LEVEL DISPLAY CARD) ARE MISSING THE
 REQUIRED SIGNATURES AND DATES.
 COMMENTS FROM LAST REVIEW:
 PROVIDE ACCURATE AREA TABULATIONS FOR THE EXISTING
 CONDITIONED AND UNCONDITIONED SPACE, AS WELL AS, THE
 PROPOSED SPACES. FBC 107.2.1
  
 7) NOT COMPLIED. A MUNICIPAL IMPACT FEE RECEIPT
 (#MU-2018-038733-0000) FROM PALM BEACH COUNTY WAS
 SUBMITTED BUT WE ARE STILL MISSING THE RECEIPTS STAMPED
 ON THE PLAN COMPLETE WITH TRACKING NUMBER.
 COMMENTS FROM LAST REVIEW:
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 8) NOT COMPLIED. A FLORIDA BUILDING CODE, ENERGY
 CONSERVATION FORM #R 402 AND (EPL) DISPLAY CARD WERE
 SUBMITTED BUT NOT SIGNED AND DATED AS REQUIRED.
 COMMENTS FROM LAST REVIEW:
 MISSING PAGES FROM FORM THAT WAS SUBMITTED. SUBMIT
 ENERGY COMPLIANCE DOCUMENTS AS REQUIRED BY THE 2017 FBC
 ENERGY CONSERVATION SECTION R101.5.
  
 9) COMPLIED; THE INFORMATION FOR DOOR SHOULD BE
 SUBMITTED UNDER SEPERATE PERMIT # 18081459.
  
 10) COMPLIED; THE INFORMATION FOR WINDOW AND DOOR TYPES
 SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # 18081459.
 PRODUCT APPROVALS FOR AN EXTERIOR DOOR #FL14320-R5 AND
 A FIXED WINDOW # FL15553-R3 WERE SUBMITTED.
  
 11) COMPLIED; THE INFORMATION FOR CASEMENT WINDOW
 SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # 18081459.
  
 12) NOT COMPLIED. THE INFORMATION FOR THE BATHROOM
 WINDOWS SHOULD BE SUBMITTED UNDER SEPERATE PERMIT #
 18081459 BUT THE PRODUCT APPROVALS ARE STILL REQUIRED
 FOR THE GLAZING OF THE SHOWER ENCLOSURE.
 COMMENTS FROM LAST REVIEW:
 SPECIFY SAFETY GLAZING FOR THE SHOWER ENCLOSURE,
 THE MASTER BATH WINDOW AT THE TUB AND THE WINDOWS IN
 THE SHOWERS IF THEY ARE WITHIN 60" OF THE SHOWER FLOOR.
 FBC?R308.4
  
 13) COMPLIED LAST REVIEW.
  
 14) COMPLIED LAST REVIEW.
  
 15) COMPLIED; THE MEANING OF KSD AND TSD WAS CLARIFIED.
 KSD=KING STUD AND TSD=TRIMMER STUD.
 COMMENTS FROM LAST REVIEW:
 CLARIFY THE MEANING OF (2) KSD AND (2) TSD ON SHEET
 S4.0 OF THE PLANS. FBC 107.2.1
  
 16) COMPLIED LAST REVIEW.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 18) NOT COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
  
  
  