| 2018-12-26 13:42:06 | ****CORRECTIONS**** |
| | |
| | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 3RD REVIEW: |
| | |
| | PLEASE ADDRESS COMMENTS BELOW: |
| | |
| | 1) COMPLIED LAST REVIEW. |
| | |
| | 2) COMPLIED LAST REVIEW. |
| | |
| | 3) COMPLIED LAST REVIEW. |
| | |
| | 4) NOT COMPLIED. WE STILL NEED THE REGISTERED DESIGN |
| | PROFESSIONAL'S SIGNATURE, SEAL, AND TITLE BLOCK ON EACH |
| | PAGE/DOCUMENT AS PER LAST REVIEW: |
| | THE STRUCTURAL PLANS ARE REQUIRED TO HAVE THE |
| | ENGINEER?S ORIGINAL HANDWRITTEN SIGNATURE IN THE TITLE |
| | BLOCK ON EACH SHEET. FAC 61G15?23.003 PROCEDURES FOR |
| | PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN |
| | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, |
| | F.S., AND RULE 61G15?23.001, F.A.C. MUST BE PHYSICALLY |
| | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE |
| | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | |
| | 5) COMPLIED (NOT APPLICABLE). |
| | |
| | 6) NOT COMPLIED. THE SUBMITTED DOCUMENTATION (FLORIDA |
| | BUILDING CODE, ENERGY CONSERVATION AND ENERGY |
| | PERFORMANCE LEVEL DISPLAY CARD) ARE MISSING THE |
| | REQUIRED SIGNATURES AND DATES. |
| | COMMENTS FROM LAST REVIEW: |
| | PROVIDE ACCURATE AREA TABULATIONS FOR THE EXISTING |
| | CONDITIONED AND UNCONDITIONED SPACE, AS WELL AS, THE |
| | PROPOSED SPACES. FBC 107.2.1 |
| | |
| | 7) NOT COMPLIED. A MUNICIPAL IMPACT FEE RECEIPT |
| | (#MU-2018-038733-0000) FROM PALM BEACH COUNTY WAS |
| | SUBMITTED BUT WE ARE STILL MISSING THE RECEIPTS STAMPED |
| | ON THE PLAN COMPLETE WITH TRACKING NUMBER. |
| | COMMENTS FROM LAST REVIEW: |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, |
| | ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO |
| | PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS |
| | WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID |
| | RECEIPT MUST BE RETURNED TO THE CITY BUILDING |
| | DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED. |
| | FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT |
| | (561) 233-5025. |
| | |
| | 8) NOT COMPLIED. A FLORIDA BUILDING CODE, ENERGY |
| | CONSERVATION FORM #R 402 AND (EPL) DISPLAY CARD WERE |
| | SUBMITTED BUT NOT SIGNED AND DATED AS REQUIRED. |
| | COMMENTS FROM LAST REVIEW: |
| | MISSING PAGES FROM FORM THAT WAS SUBMITTED. SUBMIT |
| | ENERGY COMPLIANCE DOCUMENTS AS REQUIRED BY THE 2017 FBC |
| | ENERGY CONSERVATION SECTION R101.5. |
| | |
| | 9) COMPLIED; THE INFORMATION FOR DOOR SHOULD BE |
| | SUBMITTED UNDER SEPERATE PERMIT # 18081459. |
| | |
| | 10) COMPLIED; THE INFORMATION FOR WINDOW AND DOOR TYPES |
| | SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # 18081459. |
| | PRODUCT APPROVALS FOR AN EXTERIOR DOOR #FL14320-R5 AND |
| | A FIXED WINDOW # FL15553-R3 WERE SUBMITTED. |
| | |
| | 11) COMPLIED; THE INFORMATION FOR CASEMENT WINDOW |
| | SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # 18081459. |
| | |
| | 12) NOT COMPLIED. THE INFORMATION FOR THE BATHROOM |
| | WINDOWS SHOULD BE SUBMITTED UNDER SEPERATE PERMIT # |
| | 18081459 BUT THE PRODUCT APPROVALS ARE STILL REQUIRED |
| | FOR THE GLAZING OF THE SHOWER ENCLOSURE. |
| | COMMENTS FROM LAST REVIEW: |
| | SPECIFY SAFETY GLAZING FOR THE SHOWER ENCLOSURE, |
| | THE MASTER BATH WINDOW AT THE TUB AND THE WINDOWS IN |
| | THE SHOWERS IF THEY ARE WITHIN 60" OF THE SHOWER FLOOR. |
| | FBC?R308.4 |
| | |
| | 13) COMPLIED LAST REVIEW. |
| | |
| | 14) COMPLIED LAST REVIEW. |
| | |
| | 15) COMPLIED; THE MEANING OF KSD AND TSD WAS CLARIFIED. |
| | KSD=KING STUD AND TSD=TRIMMER STUD. |
| | COMMENTS FROM LAST REVIEW: |
| | CLARIFY THE MEANING OF (2) KSD AND (2) TSD ON SHEET |
| | S4.0 OF THE PLANS. FBC 107.2.1 |
| | |
| | 16) COMPLIED LAST REVIEW. |
| | |
| | 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | 18) NOT COMPLIED. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED |
| | AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | |
| | |
| | |