Plan Review Notes
Plan Review Notes For Permit 18070454
Permit Number 18070454
Review Stop E
Sequence Number 2
Notes
Date Text
2018-08-08 06:13:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. TANKLESS WATER HEATER AND LOCATION OF NEW INTERIOR
 PANEL NOT ON PLAN, PROVIDE LOCATION. FBC 107.2.1
  
 2. MINIMUM OF 2 GROUND RODS REQUIRED 250.53A2 NEC
  
 3. PROVIDE RISER DIAGRAM OF EXISTING RESIDENTIAL
 SERVICE. OVERHEAD SERVICE? UNDERGROUND SERVICE? WIRE
 SIZE? NEC 220.16A1&2, 220.12, 220.14
 FBC RE 3602.1, FBC RE 3602.2, FBC 107.2.1
  
 4. A/C COMPRESSORS AND AHU'S FED FROM METE/MAIN COMBO
 NOT IN LOAD CALC, ALSO TANKLESS WATER HEATER NOT IN
 LOAD CALC. PROVIDE ACCURATE LOAD CALCULATION INCLUDING
 ALL LOADS. NEC 220; FBC RE E3602.2
  
 5. HOUSE HAS ATTACHED GARAGE. SMOKE ALARMS OF OUTSIDE
 OF BEDROOMS MUST BE SMOKE/CARBON MONOXIDE COMBINATION
 ALARMS WITHIN 10'. FBC R 315.1 FBC R 315.13
  
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS FOR ALL PANELS (METER/MAIN COMBO HAS NO PANEL
 SCHEDULE), THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4;
 WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 INFORMATIONAL NOTE: TO MY KNOWLEDGE A 300AMP METER/MAIN
 COMBO IS NOT SOLD PLEASE VERIFY AND PROVIDE MORE
 INFORMATION. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  