2018-08-30 14:00:441ST REVIEW: FBC 2017 6TH EDITION
 DENIED
  
 GENERAL COMMENT:PLAN SHEET T-0 INDICATES APPLICABLE
 CODES ARE FBC 5TH ADDITION; APPLICABLE CODES ADOPTED BY
 WPB ARE 6TH ADDITION. PLEASE COMPLY
  
 GAS REVIEW
  
 1. SUBMIT MANUFACTURERS SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2; INCLUDE
 TANKLESS WATER HEATER, RANGE AND DRYER
  
 2. DRYER AND TANKLESS WATER HEATER ARE SHOWN ON RISER
 DIAGRAM AND IN THE CALCULATIONS. PLEASE SHOW LOCATIONS
 ON PLAN.
 THE TANKLESS HEATER IF MOUNTED ON BUILDING EXTERIOR
 SHALL BE MOUNTED A MIN OF 4' FROM ANY OPENING IN
 BUILDING OR IF INSIDE REQUIRES COMBUSTION AIR FROM
 OUTSIDE AND EXHAUST VENT TO OUTSIDE IN ACCORDANCE WITH
 FBC G2407 AND MANUFACTURERS SPECS.SHOW VENT AND EXHAUST
 ROUTING ON PLAN.
  
 3. PLEASE SHOW METER ON THE FLOOR PLAN. PER WPB AMEND
 TO FBC 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711